1-866-494-4610

Honeywell RA890F1288 120 Vac Protectorelay

Honeywell RA890F1288 120 Vac Protectorelay
Images for general purposes only. Actual may be different than depicted.
Honeywell RA890F1288 120 Vac Protectorelay

Honeywell RA890F1288 120 Vac Protectorelay

SKU: RA890F1288
Rating:
* This Product is Now Obsolete
0
0
0
0
0
RA890F1288
Honeywell RA890F1288 120 Vac Protectorelay

Primary control provides solid state, electronic flame safeguard protection for industrial and commercial single or dual fuel burners for rectification type flame detection.

Features: Uses rectification principle of electronic flame detection. Replaces RA890E in most applications and mounts on same Q270A1024 Subbase. Recycles if flame signal lost while in Run. Failure to establish pilot results in a lockout. Safe-start check prevents start-up if flame-simulating failure occurs in flame detector circuit. Includes built-in protection against ignition crossover in flame rod systems. Includes SPDT alarm contacts. Solid state circuitry. Mounts and removes easily through use of captive mounting screws. Mounting base is made of strong thermoplastic.
Voltage
Frequency 50 Hz; 60 Hz
Flame Failure Response Time 3.0 sec
Safety Switch Timing 15 seconds
Alarm Relay Switching SPDT

Q & A: Ask the Questions, share answers